Description
 

Flexible AC Current Clamp Fluke i3000s Flex-24 - description: 

Fluke i3000s Flex-24 is an AC current clamp utilizing the Rogowski principle. It can be used to measure currents up to 3000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.

Fluke i3000s Flex-24 – Features

  • Three ranges: 30 A, 300 A & 3000 A; 1, 10 or 100 mV/A output
  • Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
  • Maximum conductor diameter 178 mm (7 in.)
  • CAT III 600V safety rating

Fluke i3000s Flex-24 – Manuals

Download Fluke i3000s Flex-24 user manual

Fluke i3000s Flex-24 – Technical Specifications

Electrical Specifications
Current ranges 30 A / 300 A / 3000 A AC rms
Output sensitivity (AC-coupled) 100 mV / 10 mV / 1 mV per A
Load impedance 100 kΩ minimum
Accuracy at +25 °C ± 1 % of range (45 Hz to 65 Hz)
Linearity 10 % to 100 % of range ± 0.2 % of reading
Noise 8 mV AC rms (30 A) / 2 mV AC rms (300 A, 3000 A)
Frequency range 10 Hz to 50 kHz (-3 dB)
Phase error < ± 1 º (45 Hz to 65 Hz)
± 10 º (at 20 kHz)
Position sensitivity with cable > 25 mm from the coupling ± 2 % of range
External field with cable > 200 mm from the head ± 1 % of range
Power supply 2 x AA/MN 1500/LR6 Alkaline, , 400 hours, low battery indicator or dedicated external power supply
Temperature coefficient ± 0.08% of reading per °C
General Specifications
Head circumference 610 mm (24 in)
Head cable diameter 14.3 mm (0.56 in)
Head bend radius 38.1 mm (1.5 in)
Cable length (head to electronics) 2 m (6.56 ft)
Output connection 0.5 m cable terminated with safety BNC connector
Operating temperature range -20 °C to +90 °C (-4 °F to 190 °F) (head)
-20 °C to +85 °C (-4 °F to 185 °F) (electronics)
Storage temperature range -40 °C to +105 °C (-40 °F to 221 °F) (head)
-20 °C to +85 °C (-4 °F to 185 °F) (electronics)
Operating humidity 15 % to 85 % (non-condensing)
Weight 180 g (0.396 lb) (head)
190 g (0.419 lb) (electronics)
Safety standards BS EN 61010-1: 2001
BS EN 61010-2-032: 2002
BS EN 61010-031: 2002
600 V rms, Category III, Pollution Degree 2
EMC standards EN 61326: 1998 +A1, A2, & A3
 